0 to 10V Analog Scaling Calculator
The 0 to 10V Analog Scaling Calculator will help you to calculate Scaling Value , Analog raw value Conversion etc
Creative Works
The 0 to 10V Analog Scaling Calculator will help you to calculate Scaling Value , Analog raw value Conversion etc
0-10V signals are widely used in RTD Sensors and various field Instruments
0 to 10V is being used as a voltage representation for field Instrumentation measurement range.
( 0 to 10V ) Signal from the Instruments, will be send to an analog Card reside in a PLC / DCS Controller.
In the PLC/ DCS Controller, the voltage signal will be converted back to its Actual Instrument value by multiplying it with a scale Constant .
The User then will be able to view the actual value of the field instruments from his / her HMI or SCADA Interface.
Brand | Min Raw Count | Max Raw Count |
---|---|---|
Allen Bradley | 6241 | 31206 |
Siemens | 5529 | 27648 |
Emerson | 800 | 4095 |
Yokogawa | -30000 | 30000 |
(1) E&I engineer went on site to measure the Analogue Output Voltage of a Temperature Transmitter . The Value recorded was 5V.
(2) He then check the Temperature Transmitter Specification Sheet . The Minimum Range is 0°C , while the Maximum range is 200°C
(3)He got the Measured Current , and want to know what is the Calculated Temperature ?
Signal Range in Voltage : 0 to 10V
Instrument Range : 0°C to 200°C
Measured Current Value : 5V
Instruments Current Value : ??°C ( This is what he wanna Find Out )
Determine the Range of the Field instrument
Range = High Limit – Low Limit
Range = 200°C – 0 °C
Analog Range = 10-0
Calculate Temperature Value base on field measured voltage
Instrument Temperature = 200 x [ 5/10 ]
= 100°C
(1) PLC Engineer is trying to convert field measure Value in Voltage to PLC Raw Value
(2) The PLC used for this Application is a Siemens PLC
(3) He Requested his Colleague to assist him to measure the Field instrument Device , His Colleague got a measurement of 5V from the Field RTD
Signal Range in Voltage : 0 to 10V
Instrument Range : 0°C to 200°C
Measured Current Value : 5V
Siemens PLC Analogue Raw Range : 5529 to 27648
Calculate PLC Raw Range
PLC Raw Range = 27648 – 5529 = 22119
Convert measured Voltage to PLC Raw Data
PLC Raw Data =[ PLC Raw Range x [ (Measured Field Voltage ) /10 ] ] + Low Raw Limit
PLC Raw Data =[ 22119 x [ (5V ) /10V ] ] + 5529
PLC Raw Data = 16589
Check Out 4 to 20mA Calculator Here